Why does the introductory machine knock out during the operation of the boiler, but the group one does not work

Hello! I have an electrode boiler of 6 kW connected to an automatic machine 32 A. The general automatic machine is 50 A. When the boiler is operating, an automatic machine 50 A. is knocked out. Tell me how to solve the problem.

Loading...

One comment

  • Admin

    If the machine knocks out 50 A, then the total load of your electrical appliances exceeds this value. A boiler of this power is a load with a single-phase connection a little more than 27 A. If, when you turn on other electrical appliances, the total load exceeds 50 A, then the machine is disconnected from the overload.