Why is the difavtomat triggered when the LED chandelier is connected?

Denis asks:
Hello! At the entrance to the house is a diffavomat. The ground loop is. Everything worked perfectly! We decided to hang LED chandeliers in three rooms. When connected to each of them, the earth immediately knocks out a differential machine.
The answer to the question:
Hello! There may be a problem in the power supply for the LEDs. Are the chandeliers the same? Phase, zero and ground on the chandelier terminal block when connected? It is also necessary to check whether there are no exposed spots on the phase and neutral conductor in the chandelier body itself - an accidental contact will trigger an RCD. This can be checked by touching the indicator screwdriver of the chandelier body with a non-connected grounding conductor. Only you need to stand, of course, not on the dielectric ladder. If the voltage indicator lights up, then look for a leak in the wiring of the chandelier itself.